Please use this identifier to cite or link to this item: https://scidar.kg.ac.rs/handle/123456789/19945
Full metadata record
DC FieldValueLanguage
dc.contributor.authorMijailovic, Vladica-
dc.contributor.authorRanković, Aleksandar-
dc.date.accessioned2024-01-18T08:35:26Z-
dc.date.available2024-01-18T08:35:26Z-
dc.date.issued2023-
dc.identifier.isbn9788682317906en_US
dc.identifier.urihttps://scidar.kg.ac.rs/handle/123456789/19945-
dc.descriptionZbornik radova 36. Savetovanja CIGRE Srbija 2023 Fleksibilnost elektroenergetskog sistema [Elektronski izvor] : 22-26. maj 2023, Zlatibor / [glavni i odgovorni urednik Nebojša Petrović]en_US
dc.description.abstractThe paper presents the procedure for calculating the switching overvoltage on the supplying circuit breaker of the MV cable feeder to which induction and/or synchronous generators are connected during a bolted three-phase short circuit. When a fault occurs, the feeder is disconnected by a circuit breaker at the beginning of the feeder. After the set delay time has expired, since island operation is not allowed, the connected distributed generators will also be switched off. It is shown that, during the period when the grid is off and the generators are on, the overvoltage factor reaches a value between 2.2 and 2.5, depending on the type of generator and the connection location. The individual responses of the distribution network and the mentioned types of distributed generators in case of failure are known and they differ significantly from each other. By using the superposition theorem, it is shown how to calculate the switching overvoltage, with the elementary use of a computer.en_US
dc.language.isosren_US
dc.rightsinfo:eu-repo/semantics/openAccess-
dc.source36. Savetovanja CIGRE Srbija - Fleksibilnost elektroenergetskog sistema, 22-26. maj 2023, Zlatiboren_US
dc.subjectSwitching overvoltageen_US
dc.subjectInduction generatoren_US
dc.subjectSynchronous generatoren_US
dc.subjectDistribution networken_US
dc.subjectSuperpositionen_US
dc.titlePRORAČUN SKLOPNIH PRENAPONA ZA SLUČAJ METALNOG TROFAZNOG KRATKOG SPOJA NA SN-IZVODU SA PRIKLЈUČENIM INDUKCIONIM I/ILI SINHRONIM GENERATORIMAen_US
dc.title.alternativeCALCULATION OF SWITCHING OVERVOLTAGES FOR THE CASE OF A BOLTED THREE-PHASE SHORT CIRCUIT ON MV-FEEDER WITH CONNECTED INDUCTION AND/OR SYNCHRONOUS GENERATORSen_US
dc.typeconferenceObjecten_US
dc.description.versionPublisheden_US
dc.identifier.doi10.46793/CIGRE36.1959Men_US
dc.type.versionPublishedVersionen_US