Please use this identifier to cite or link to this item: https://scidar.kg.ac.rs/handle/123456789/18865
Title: The Static Characteristic of the Evaporator Superheat Control Loop
Authors: Pršić, Dragan
Vičovac, Aleksandar
Stojanović, Vladimir
Issue Date: 2016
Abstract: One of two primary control loops of the vapour compression cycle-based system is the evaporator superheat control loop. Its function is to protect the components from damage and increase the energy efficiency of the system. The process part of the loop consists of the electronic expansion valve and the evaporator. The paper presents the static characteristic of the process part. The characteristic is determined experimentally on the water-to-water domestic heat pump installation. The input is the control signal of the valve, and the output is the evaporator superheat temperature. The static characteristic is static, multivalued nonlinearity with hysteresis and saturation on one side. Using the approximation of nonlinearity by means of linear segments, the simulation results in obtaining the describing function of the static characteristic.
URI: https://scidar.kg.ac.rs/handle/123456789/18865
Type: conferenceObject
Appears in Collections:Faculty of Mechanical and Civil Engineering, Kraljevo

Page views(s)

26

Downloads(s)

10

Files in This Item:
File Description SizeFormat 
saum2016_prsic.pdf346.49 kBAdobe PDFThumbnail
View/Open


Items in SCIDAR are protected by copyright, with all rights reserved, unless otherwise indicated.